A latch-side approach to a sliding of folding door requires a min.requirement beside the door on the latch side, and so the clear space box may slide left or right as necessary in front of the door in this scenario.Īccessible Door - Slide Side approach to Sliding or Folding Door A slide-side approach to a sliding or folding door requires a clear space in front of the door measuring a min.of 48” clear space in front of the door.Īccessible Door - Sliding or Folding door Front Side approach A front approach to a sliding or folding door only requires that there is a min.of 24” of wall on the latch side of the door.Īccessible Door - Latch Side approach Push Side of 42” (48” if the door also has a closer) of clear space in front of the door and a min. For a latch-side approach on the push side of a swinging door, there must be a min.of 24” of wall on the latch side of the door.Īccessible Door - Latch Side approach Pull Side of 48” (54” if the door also has a closer) of clear space in front of the door and a min. For a latch-side approach on the pull side of a swinging door, there must be a min.requirement beside the door on the latch side, and so the clear space box may slide left or right as necessary in front of the door in this scenario.Īccessible Door - Hinge Side approach Push Side of 54”x48” if the door includes both a closer and a latch. For a hinge-side approach on the push side of a swinging door, there must be a clear space in front of the door that measures 54”x42”.of 54”.Īccessible Door - Hinge Side approach Pull Side clear space in front of the door may be reduced to a min. of 42” of wall to the handle side of the door, then the min. of 60” clear in front of the door and 36” of wall to the latch side of the door. For a hinge-side approach on the pull side of a swinging door, there must be a min.If the door does not have both a closer and latch, there is no minimum wall requirement.Īccessible Door - Front Approach Push Side of 12” of wall on the latch side if the door has both a closer and latch. When approaching a swinging door in a forward direction from the push side, there should be a min.of clear floor in front of the door.Īccessible Door - Front Approach Pull Side of 18” of wall (24” preferred) on the latch side of the door and 60” min. When approaching a swinging door in a forward direction from the pull side, there should be a min.The door shall provide the minimum maneuvering clearances detailed below:.Accessible Doors should not take more than 5 pounds of force to open.Door closers must be adjusted to take a minimum of 3 seconds to move 3 inches from a open position of 70°.Door handles must be no higher than 48” above the finished floor. Accessible Door hardware and handles at accessible doors must have a shape that is easy to grasp with one hand and does not require tight grasping, pinching or twisting of the wrist to operate.Raised thresholds must be beveled with a slope no greater than 1:2. Exterior sliding doors are excepted and allowed to have a threshold of up to ¾” in height. Thresholds at accessible doorways cannot exceed ½” in height.Two doors in series must have a minimum of 48” in addition to the width of the door(s) swinging into the space ( so a 36” door swinging into a hall would require the hall to be a minimum of 7’-0” long before any other door could be placed, if the second door does not also swing into the hall).This is why a 36” door is commonly used excepting at metal bathroom stall partitions where the door is significantly thinner. This means that the door width must be approximately 34” or larger due to the thickness of the door. The minimum clear opening must be 32” with the door open 90°.At least one side of any double-leaf doorways with independently operated doors must meet the criteria. A revolving door or turnstile cannot be the only means of passage at an accessible entrance or along an accessible route.The following rules apply in order for a door to be considered accessible: The requirements state, however, that it is preferable if ALL entrances are accessible. This percentage excludes specially considered accessible entrances such as those from parking garages, tunnels, or elevated walkways from which all entrances must be accessible. The standards state that a minimum of 50% of all public entrances to the building must be accessible, there must be at least one accessible entrance to all tenancies and the number of accessible entrances must be at least equivalent to the number of exits required by the building and/or fire codes.
0 Comments
Leave a Reply. |